Model SRAN Remote Annunciator
Congratulations, and thank you for purchasing Setra’s Remote Annunciator (SRAN).
S
etra’s Remote Annunciator (SRAN) provides remote indication of room pressure
status.
Mounting
The SRAN is the same size as a standard electrical wall plate (2.75” W x 4.5” H) and
ts fl ush to the wall. It can be mounted to the wall using a standard electrical box.
Green LED
Acknowledge
Switch
Audible
Alarm
Specifi cations
Enclosure
2.75 “W x 4.5 H H stainless steel wall cover plate
External Supply
15 VDC, 50 mA Max.
Display Panel
Green and Red LED indicators, and
Acknowledge Switch
Audible Alarm
0 to 85 dBA measured 4 inches from anunciator
Acknowledge Switch
Momentarily turns off the audible alarm
Operation
Under normal conditions the Green LED remains on. When an alarmed condi-
tion occurs (i.e., room pressure falls outside preset range), a signal is triggered
by the room pressure monitor, the Green LED shuts off, the Red LED fl ashes and
the Audible Alarm sounds. The acknowledge button can be pressed to momen-
tarily turn-off the Audible Alarm, and the Red LED will continue to fl ash until the
alarmed condition is corrected. When the alarmed condition is corrected the
annunciator will reset itself. The Green LED will turn-on, the Red LED and Audible
alarm will shut-off.
Model SRAN Remote Annunciator
Installation Instructions
Zobrazit stránku 0
1 2 3 4

Shrnutí obsahu

Strany 1 - Installation Instructions

Model SRAN Remote Annunciator Congratulations, and thank you for purchasing Setra’s Remote Annunciator (SRAN). Setra’s Remote Annunciator (SRAN) pro

Strany 2 - Customer

Alarm Relay OutputThe Single Pole Double Throw (SPDT) relay output can be used for remote signal-ing of alarm condition. A form “C” contact rated at 1

Strany 3

Model SRAN PC Board ViewAudible AlarmAlarm potentiometer adjusts from 0 to 85 dBA. Using a screwdriver, rotate potentiometer clockwise to increase vol

Strany 4 - RETURNING PRODUCTS FOR REPAIR

RETURNING PRODUCTS FOR REPAIRBefore returning the unit for repair, please contact a Setra application engineer (800-257-3872, 978-263-1400) to review