3.3 Remote Sensors Installation
Cable Version (P/N: 231GRSX4MXXXX)
For cable version remote sensors, use the following instructions:
1. Install the remote sensors into the system plumbing (use 3/4” hex to tighten”)
Important:
Each remote sensor is labeled “HIGH PRESSURE SENSOR or “LOW PRESSURE SENSOR”, respectively. Match up
the high pressure sensor to the high “HI (+)” pressure electrical terminals, and the low “LO (-)” pressure
sensor to the low pressure electrical terminals. Otherwise, the performance may not meet the product
linearity specications.
2. Attach the cable provided to the 3-Pin Packard connector on the remote sensor.
3. Feed the cable through the PG tting on the bottom of the unit and tighten the tting.
4. Remove the terminal blocks from the circuit board and use the following chart:
Important: Prior to putting the unit into service, complete conguration setup in Section 4. After conguration is
complete, press the “Zero button.
IN
MM
3.00
76.0
1.46
37.1
0.325
8.3
1.62
41.2
Chart 2. Electrical wiring color chart
for High & Low Pressure sensors (Cable
version)